| Technical specifications for Goldgear GG61F5 |
| Power range |
| BB61F5 |
1-300 kW 400V |
| 0.0-22 kW 200V |
| Main conection |
| Input Voltage |
[400 V] 304-460 V [+ - 20%] |
| [200 V]176-266 V [+ - 20%] |
| Input Frequency |
40 - 66 Hz |
| Motor conection |
| Output Voltage |
0 - Uin |
| Continuous output current |
V/F 150 % 1 min, Vector180% 1min |
| Output Frequency |
0 - 300 Hz |
| Frequency Resolution |
0.01 Hz |
| Control Characteristics |
| Control Method |
V/F control,Vector control[VEC],Sensorless Vector Control[SSL] |
| Frequency res.Analog Input |
Resolution 12 Bit,accuracy +/- 1 % |
| Frequency ref, Penel ref. |
Resolution 0.01 Hz |
| Switching Frequency |
1-15 kHz |
| Field weakening |
50 - 600 Hz |
| Breaking torque without break resistor |
30 % DC brake |
| Torque Response |
50 microSEC for Vector Control |
| Protective function |
| Over current protection |
Yes |
| Over voltage protection |
Trip limit 1.2 x Uin |
| Under voltage protection |
Trip limit 0.8 x Uin |
| Motor overload protection |
Electronic thermal overload relay |
| Motor stall protection |
Yes |
| Unit over temperature protection |
Yes |
| Current limit protection(Hardware/Software) |
Yes |
| Control connection |
| Analog Voltage |
0 - 10 V, +/- 0 -10 V,R = 1-5kOHM |
| Analog Current |
4-0 mA,R1- 250 OHM,differential |
| Digital input |
5 pcs,(Programable) |
| Auxilary voltage output |
10 VDC max 100mA |
| Analog output |
0-10 V,x2 Channel(Programmable) |
| Relay output |
2 pcs/300 VDC, 250 VAC |
| Digital output |
2 pcs/open collector input |
| Enclosure |
| GG61F5 |
|
|
Type
|
|
Cooling air flow requierment |
Normianl ratings |
NO overload used |
Light overload used |
Heavy duty use |
|
Noise level |
Heat dissipation |
Air flow |
I cont.max
A |
i max
A |
P constant
kW |
In
A |
Pn
|
I nd
A |
P nd
kW
|
Frame size
|
dBA
|
W
|
m3/h
|
Three phase supply voltage 380,400,or 415 V,The power rating are valid at nominal voltage(400V) |
GG61F5-001-4 |
2.8 |
3.44 |
0.75 |
2.6 |
0.75 |
2.2 |
0.37 |
R0 |
60 |
95 |
45 |
GG61F5-002-4 |
3.9 |
4.6 |
1.5 |
3.6 |
1.5 |
3.0 |
0.75 |
R0 |
60 |
105 |
45 |
GG61F5-003-4 |
5.2 |
6.2 |
2.2 |
4.8 |
2.2 |
3.8 |
1.5 |
R0 |
60 |
125 |
45 |
GG61F5-005-4 |
7.6 |
9 |
3.7 |
7.0 |
3.7 |
6 |
2.2 |
R1 |
62 |
165 |
70 |
GG61F5-008-4 |
12 |
14 |
5.5 |
11 |
5.5 |
9 |
3.7 |
R1 |
62 |
210 |
80 |
GG61F5-010-4 |
15.5 |
18 |
7.5 |
14 |
7.5 |
12 |
5.5 |
R1 |
62 |
260 |
80 |
GG61F5-015-4 |
23 |
27 |
11 |
21 |
11 |
18 |
7.5 |
R2 |
62 |
345 |
110 |
GG61F5-020-4 |
29 |
34 |
15 |
26 |
15 |
22 |
11 |
R2 |
62 |
430 |
110 |
GG61F5-025-5 |
37.5 |
44 |
18.5 |
34 |
18.5 |
27 |
15 |
R2 |
62 |
480 |
110 |
GG61F5-030-4 |
41 |
48 |
22 |
38 |
22 |
32 |
18.5 |
R2 |
62 |
535 |
110 |
GG61F5-040-4 |
56 |
65 |
30 |
53 |
30 |
39 |
22 |
R3 |
62 |
620 |
110 |
GG61F5-050-4 |
68 |
80 |
37 |
64 |
37 |
48 |
30 |
R3 |
65 |
800 |
180 |
GG61F5-060-4 |
82 |
96 |
45 |
78 |
45 |
60 |
37 |
R3 |
65 |
995 |
180 |
GG61F5-075-4 |
110 |
128 |
55 |
107 |
55 |
80 |
45 |
R4 |
65 |
1200 |
400 |
GG61F5-100-4 |
140 |
165 |
75 |
137 |
75 |
100 |
55 |
R4 |
65 |
1440 |
400 |
GG61F5-125-4 |
165 |
195 |
90 |
161 |
90 |
120 |
75 |
R5 |
65 |
1940 |
400 |
GG61F5-150-4 |
190 |
224 |
110 |
185 |
110 |
150 |
90 |
R5 |
71 |
2310 |
620 |
GG61F5-200-4 |
256 |
302 |
150 |
250 |
150 |
210 |
110 |
R5 |
71 |
3800 |
620 |
GG61F5-250-4 |
321 |
378 |
180 |
315 |
180 |
290 |
150 |
R5 |
72 |
4400 |
1200 |
GG61F5-300-4 |
386 |
454 |
220 |
380 |
220 |
320 |
180 |
R6 |
72 |
5000 |
1200 |
GG61F5-350-4 |
425 |
500 |
260 |
420 |
260 |
380 |
220 |
R6 |
72 |
6180 |
1200 |
|
Type
|
|
Cooling air flow requierment
|
Normianl ratings
|
NO overload used |
Light overload used
|
Heavy duty use
|
|
Noise level |
Heat dissipation |
Air flow |
I cont.max
A |
i max
A |
P constant
kW |
In
A |
Pn
|
I nd
A |
P nd
kW |
Frame size
|
dBA
|
W
|
m3/h
|
Single phase or three phase supply voltage 200,220,or 230 V,The power rating are valid at nominal voltage(200V)
|
GG61F5-0.5-2 |
2.75 |
3.2 |
0.37 |
2.6 |
0.37 |
2.1 |
0.2 |
R0 |
35 |
85 |
25 |
GG61F5-001-2 |
4.3 |
5 |
0.75 |
4.0 |
0.75 |
3.8 |
0.37 |
R0 |
35 |
115 |
25 |
GG61F5-002-2 |
6.8 |
8 |
1.5 |
6.2 |
1.5 |
5.8 |
0.75 |
R0 |
35 |
150 |
25 |
GG61F5-003-2 |
9.5 |
11 |
2.2 |
9.1 |
2.2 |
7 |
1.5 |
R1 |
35 |
200 |
25 |
GG61F5-005-2 |
14.5 |
17 |
3.7 |
14 |
3.7 |
11 |
2.2 |
R1 |
62 |
250 |
80 |
GG61F5-008-2 |
22 |
25 |
5.5 |
21 |
5.5 |
16 |
3.7 |
R1 |
62 |
360 |
80 |
GG61F5-010-2 |
28 |
33 |
7.5 |
27 |
7.5 |
21.5 |
5.5 |
R2 |
62 |
430 |
80 |
GG61F5-015-2 |
41 |
48 |
11 |
40 |
11 |
32 |
7.5 |
R2 |
62 |
535 |
80 |
GG61F5-020-2 |
52 |
60 |
15 |
50 |
15 |
37 |
11 |
R2 |
65 |
600 |
180 |
GG61F5-025-2 |
67 |
78 |
18.5 |
65 |
18.5 |
46 |
15 |
R3 |
65 |
790 |
180 |
GG61F5-030-2 |
72 |
84 |
22 |
70 |
22 |
53 |
18.5 |
R3 |
65 |
820 |
180 |
Type |
Ip21 |
 |
H
mm |
W
mm |
D
mm |
R0 |
165 |
110 |
165 |
R1 |
360 |
215 |
180 |
R2 |
470 |
265 |
255 |
R3 |
665 |
320 |
265 |
R4 |
905 |
460 |
340 |
R5 |
1400 |
530 |
450 |
R6 |
1800 |
790 |
600 |
*Weights are for the basic configuration with switch fuse,but without contactor and other option.
| Nomianl Rating : |
Icont.max : rated current available
continuously without overloadability at
40 degree c |
Imax : maximum output current.Available for 10 s at
start,ohterwise as long as allowed by drive
temperature.
Note : max.motor shaft power is 150% Pnd
|
| Typical Rating : |
No-overload use
Pcont.max : typical motor power in no-overload use. |
Lignt-overload use
In : continuous current allowing 110% In for 1 min/5min at 40 Degree C
Pn : typical motorpower in lignt-overload use
|
| Heavy-duty |
Id : continuous current allowing 150 % Ind for 1 min/5 at 40 Degree C |
Pnd : typical motorpower in heavy-duty use current rating are the same
regradless of the supply voltage within ont voltage range The rating
apply in 40 degree C ambient temperature.In lower temperatures the
ratings are higher(except Imax) |
BASIC SCHEMATIC DIAGRAM
 |
DIGITAL AUTOMATIC EVACUATION SYSTEM
use for elevator system,in the elavator of main power failure or building is fire
- Digital DSP Microprocessor
- if the elevator stop between floors,or with door close
- the device automatically turn-on and run to the nearest floor and
reopening the door.
- 2 line x 16 Character. LCD operator
- Use the microprocessor control setting program and digital asjust
replace to analog adjust
- Have Display show statuss of useand battery
- Easy installation ,Easy Setting and small size
- 48 V battery,Sealed Lead Time without mainenance
- Economy cost
|
|
| SPECIFICATION |
|
170/220/380/415 V 3 Phase 50/60 Hz |
|
60/70/110/180/220/240 VDC(max 200 watt) |
|
AC or DC programable for DC drive or inverter drive 60 70 110 180 240 programmable(max 200 watt) |
- Floor detect sensor supply
|
24 VDC |
|
220 VAC (max 100 watt) |
|
Over run safety programable NO/NC
Safety 1 programmable NO/NC
Safety 2 programmable NO/NC |
|
Can be select NO/NC programmable or common |
|
Door open limit switch can be select NO/NC programable |
- Signal for open door motor
|
NO contact can be set the operate time of contact |
|
Sealed lead type battery |
|
"LCD" 2 line 16 charactor and status lcd display |
|
closeloop current Charger Control |
- Protection of equipment supply
|
Short circuit supply output protection
And fuse protection for carlamp / 24 VDC / door motor |
|
3 phase detection |
|
-10 to +50 degree C |
|
90 % RH or less(no conden sation) |
|
Max 100 m above sealevel max 5.9m (0.6g) |
|
| Protection Specification |
| LCD display mode trip |
- Over current (Traction motor over current)
|
- Over voltage (Battery over voltage)
|
- Under voltage (Battery under voltage)
|
|
|
|
- Charger fail ( battery loss)
|
| FUNCTION TABLE OF AUTOMATIC EVACUATION SYSTEM |
| |
FAC.SET |
DESCRIPTION |
DATA |
Output frequency |
04.0 |
Output frequency for traction motor |
0 - 50 Hz |
Boost voltage |
03 |
Troque boost of traction motor |
0 - 10% |
Accel time |
05 |
Accellerate time of traction motor |
0 - 9999 |
Motor rated freq. |
50 |
Base frequency of traction motor |
0 - 5 |
Motor rated volt |
380 |
Base voltage of traction motor |
0 - 380 |
Mech.break volt |
110 |
Supply for machine break |
60 - 240 |
Door operate type |
AC |
Door operate control type |
AC / DC |
Door operated volt |
110 |
Supply for door operate control |
60 - 240 |
Floor detect cont. |
NO |
Type of floor detect sensor contact |
NO /NC |
Door open cont. |
NO |
Type of door open limit contact |
NO /NC |
Over run cont. |
NO |
Type of over run safety limit contact |
NO /NC |
Safety switch#1 |
NO |
Type of safety switch 1 contact |
NO /NC |
Safety switch#2 |
NO |
Type of safety switch 2 contact |
NO /NC |
Max operate time |
220 |
Max operate time of aes |
0 - 9999 |
Start time delay |
05 |
Delay time before aes operate |
0 - 9999 |
FL.detect delay |
00 |
Delay time to stop traction after floor detected |
0 - 9999 |
Door operate time |
10 |
Time for NO contact to door open control |
0 - 9999 |
Delay to finish |
10 |
Delay timr after door open O.K. |
0 - 9999 |
Factory setting |
NO |
Set the data to factory setting sata |
Y / N |
Program lock |
NO |
Program lock |
Y / N |
Direction search |
YES
|
Select direction searching or not |
Y / N |
Max amp allowed |
15.0 |
Set the rated current for check direction to light wight |
0 - 9999 |
| Selection Guide |
Model |
MOTOR RATINGI |
BATTERY |
170 V |
220 V |
380 V |
415 V |
A |
kW(HP) |
kW(HP) |
kW(HP) |
kW(HP) |
|
GG-AES 010 |
3(4) |
4(5.5) |
7.5(10) |
8.5(12) |
18 |
4 BATT 48 V (12v -12Ah x 4) |
GG-AES 015 |
4(5) |
6.38(8.5) |
11(15) |
12(16) |
25 |
4 BATT 48 V (12v -7Ah x 4) |
GG-AES 020 |
5.5(7.5) |
7.5(10) |
15(20) |
17(23) |
34 |
5 BATT 60 V (12v -7Ah x 5) |
GG-AES 025 |
7.5(10) |
10.5(14) |
18(25) |
20(27) |
44 |
5 BATT 60 V (12v -7Ah x 5) |
GG-AES 030 |
8.5(12) |
12.6(17) |
22(30) |
24(32) |
50 |
5 BATT 60 V (12v -7Ah x 5) |
GG-AES 040 |
11(15) |
18(25) |
30(40) |
29(38) |
70 |
5 BATT 60 V (12v -12Ah x 5) |
| DIMENSION |
|
|
kW |
1.5 kW - 15 kW |
18.5 kW - 30 kW |
 |
W |
420 mm. |
510 mm. |
H |
700 mm. |
900 mm. |
D |
230 mm. |
280 mm. |
BASIC SCHIMATIC DIAGRAM |
 |
|